FEATURES

1.Free Prescaler setting
2.EEPROM back up system
3.Conting Frequency select 30Hz/300Hz/1KHz/3KHz
4.Multiply Range input and range output selected
5.All teh function can operate from the panel key
1. ORDERING CODE
2.MODEL AND SPECIFICATION
Model Preset stage Display digit counting range Input signal Max.Counting cps
TE-C48P41B 1 Stage 4 digit 0-9999 4-30V 10KHz
TE-C48P81B 1 Stage 8 digit 0-99999999 4-30V 10KHz
TE-C72P41B 1 Stage 4 digit 0-9999 4-30V 10KHz
TE-C72P81B 1 Stage 8 digit 0-99999999 4-30V 10KHz
TE-C49P62A 1 Stage 6 digit 0-999999 4-30V 500KHz
3. SPECIFICATIONS
Power voltage AC90-250V (50HZ/60HZ)
Consumption ¡Ü5VA (at AC 220V 50HZ
Display range 6 digit :-999999-999999
Input signal touch input,collector input,sensor input, inout resistance 5K¦¸,low calm 0-2V,high calm 4-30V
measuring DC 12V¡À10% 50mA max
overflow When measuring £¦#118alue came 6 digit ,display "-------"
reposition mode hand repositon,self repostion, outside add signal repostion
output mode N,F,C,R
input mode addution,subtration,add-sub(each other difference input)
assustabt voltage DC 12V¡À10% 50mA max
Insulation voltage 100M/min (Between lead electric end and bare very using metal,not connect touch)
Insulation strength AC200V,50HZ/60HZ 1min (Between lead electric end and bare very using metal,not connect touch)
anti-jamming Use noise anti-jammingsirnulatorside wave disturb:+2KV(between power end)¡¢+500V (between input end)
work condition 0-50¡æ 45%-85%RH
4.CONNECTION DIAGRAM
5.THE OUTSIDE DIMENSION
6.CAUTIONS
1.The meter must be heating 15 minutes with the power on before use.
2.Use in ambient temperatures of 0¡æ to 40¡æ,humidifies of 85% R.H.
3.The meter alignment interval time is one year.
4.If the input signal is superimposed with high-frequency noise,use a High-pass filter in the input signal line.
5.Input wire should not be too long. If measured signal and meter is long, please use a 2-core shielded cable, and connect its outer shite to the LO side at a signal soure.
6.If the digit meter relay is not used for a long time. Please counect power supply once every three months, not less
than 4 hours each time.